Today we finally completed the project of main circuit breaker modifications, installation of new distribution panels and connection of additional UPS.
This represents another planned phase of electrical installation expansion at our DC6. The reason is the growing number of servers, interest in housing services and requirements of our current customers. The implementation involved: • Replacement and commissioning of another UPS for network B, this time a 100 kVA UPS Eaton 93PM, which is designed for use in the most demanding IT environments with a backup time of 10
minutes (at full load). • M
odification and modernization of the main distribution panel and new 2x 260 A circuit breakers. • Reconstruction of contactors and ATS (automatic transfer switch between grid and UPS with motor generator) • Final testing of protection systems during night hours for both networks A and B for redundant power supply of server hosting and rack housing services was completed without any problems. We now have capacity and power utilization just under 35%, which provides sufficient dimensioning for our peace of mind
and that of our customers. For Greendata s.r.o. Zdeněk Maršál